Interface flap For earth leakage circuit-breakers

Article number: SZ 2482.600

According to the EN 60 204-1 standard, all power circuits with a rated current of ≤ 20 A that supply the outlets in or on machine enclosures must be protected by means of a residual-current device with a rated differential current ≤ 30 mA. Prepared for the installation of commercially available, 2-pole FI/LS circuit breaker.

Article number:
SZ 2482.600
Version
Spring terminals max. 2 x 2.5 mm², connection at rear
Product description
According to the EN 60 204-1 standard, all power circuits with a rated current of ≤ 20 A that supply the outlets in or on machine enclosures must be protected by means of a residual-current device with a rated differential current ≤ 30 mA. Prepared for the installation of commercially available, 2-pole FI/LS circuit breaker.
Benefits
Protection against leakage currents and overload
Standard-compliant protection as per EN 60 204
The ground fault circuit interrupter can be reset without opening the enclosure
Spring mechanism raises the unclosed cover 30°. This makes it impossible to forget to close the cover.
Applications
as programmer interface for controllers
as maintenance access for networks
For temporary connection of additional equipment
For quick connection to existing network structures
for programming and maintenance of integral components
Function principle
The snap fit closure ensures a good seal. The cover can be locked if necessary.
Material
Mounting frame: Plastic PBT (black)
Plastic flap: Polycarbonate (semi-transparent)
Supply includes
Interface flap, complete, consisting of plastic frame, outlet (VDE), RJ 45 (socket/socket, Cat 5e) and cut-out for ground fault circuit interrupter
Knockouts for USB A (socket/socket) provided
3 mm double-bit with insertable rotary knob
Mounting cut-out
Width of opening: 117 mm
Cut-out height: 91 mm
( Width of opening: 4.61 ˝
Cut-out height: 3.58 ˝ )
Note
interface flap may only be used when a ground fault circuit interrupter is fitted
Dimensions
Width: 131 mm
Height: 127 mm
( Width: 5.16 ˝
Height: 5 ˝ )
Rated operating voltage
250 V, 1~, 50 Hz/60 Hz
Rated current 230 V, 50 Hz
10 ‐ 16 A
Protection category IP to IEC 60 529
IP 65
Packaging unit
1 pc(s).
Weight/packaging unit
0.58 kg
( 1.3 lb. )
Customs tariff number
85366990
EAN
4028177803732
ETIM 7.0
EC002625
ECLASS 8.0
27189234
Product description
SZ Interface flap, complete, mounting frame and interface inserts, with plastic flap, semi-transparent, RJ45, sockel modules Germany, knock-out for RDC protective switch
Declarations
Declaration of conformity
Documentation
Instructions
Data sheets
General technical information
Technical details