- Article number:
- SV 9341.050
- Material
- Polyamide
Fire protection corresponding to UL 94-V0
- Color
- RAL 7035
- Rated operating voltage
- 1000 V, 3~
- 1500 V (DC)
- Electrical UL ratings (SCCR)
- 14 kA - 600 V, support spacing 500 mm, busbars PLS 800
- 22 kA - 600 V, support spacing 200 mm, busbars PLS 800
- 50 kA - 600 V, support spacing 250 mm, PLS 800 busbars, circuit breaker max. 600 A, DIVQ/7
- 50 kA - 600 V, support spacing 250 mm, busbars PLS 800, fuse class L max. 800 A, JDDZ/7
- 65 kA - 480 V, support spacing 150 mm, PLS 800 busbars, circuit breaker max. 600 A, DIVQ/7
- 65 kA - 600 V, support spacing 150 mm, busbars PLS 800, fuse class max. 600 A, JDDZ/7
- Note on Model No.:
- The use of a base tray is required for UL applications.
- UL approval only applies in conjunction with AC application
- Top-mounting
- Yes
- Number of poles
- 3-pole
- Suitable for busbars
- PLS 800
- With internal attachment
- Yes
- Center-to-center spacing of busbars
- 60 mm
- Packaging unit
- 4 pc(s).
- Net weight
- 0.32 kg
- Gross weight
- 0.361 kg
- Customs tariff number
- 85469010
- EAN
- 4028177525634
- ETIM 9
- EC001166
- ECLASS 8.0
- 27400607
- Product description
-
SV Busbar support, PLS 800, 3-pole, 60 mm bar centre distance, UL design