Busbar Supports For Flat Copper Busbars

Article number: SV 9340.050

For flat copper bars up to 800 A.

Article number:
SV 9340.050
Material
Polyamide
Fire protection corresponding to UL 94-V0
Color
RAL 7035
Rated operating voltage
1000 V, 3~
1500 V (DC)
Electrical UL ratings (SCCR)
14 kA - 600 V, support spacing 500 mm, busbars 12 x 5/10 mm
22 kA - 600 V, support spacing 500 mm, busbars 15 x 5 - 25 x 10 mm
25 kA - 600 V, support spacing 250 mm, busbars 12 x 5/10 mm
25 kA - 600 V, support spacing 500 mm, busbars 30 x 5/10 mm
30 kA - 600 V, support spacing 250 mm, busbars 15 x 5 - 25 x 10 mm
50 kA - 600 V, support spacing 350 mm, busbars 30 x 5/10 mm, Fuse Class L max. 800 A, JDDZ/7
54 kA - 600 V, support spacing 500 mm, busbars 30 x 5/10 mm, circuit breaker max. 600 A, DIVQ/7
65 kA - 480 V, support spacing 250 mm, busbars 30 x 5/10 mm, circuit breaker max. 600 A, DIVQ/7
73 kA - 600 V, support spacing 250 mm, busbars 30 x 5/10 mm, fuse class L max. 800 A, JDDZ/7
Note on Model No.:
The use of a base tray is required for UL applications.
UL approval only applies in conjunction with AC application
Number of poles
3-pole
With internal attachment
Yes
Center-to-center spacing of busbars
60 mm
Suitable for busbars
12 x 5 - 30 x 10 mm
Packaging unit
4 pc(s).
Net weight
0.668 kg
Gross weight
0.72 kg
Customs tariff number
85369010
EAN
4028177525573
ETIM 9
EC001166
ECLASS 8.0
27400607
Product description
SV Busbar support, 3-pole, 60 mm centre-to-centre spacing, for busbar WxH: 12x5-30x10 mm, UL version
Approvals
ABS
DNV-GL
Lloyds Register of Shipping
UL + C-UL (listed)
Declarations
Declaration of conformity
Declaration of conformity UK
Documentation
Additional information
Instructions
Safety instructions
Data sheets
General technical information
Short-circuit resistance diagram
Technical details