- Артикул №.:
- SK 3189.340
- Design
- wall-mounted
Outdoor - Product description
- The energy-efficient wall-mounted cooling unit Blue e+ Outdoor can be used worldwide, thanks to its multi-voltage capability, and is suitable for use with Toptec project solutions, for example.
- Benefits
- Average 75% energy savings thanks to speed-regulated components and heat pipe technology
- Longer service life of the components inside the enclosure and the cooling unit due to component-friendly cooling
- Intuitive operation due to touch display and intelligent interfaces
- Material
- Aluminium AlMg3
- Surface finish
- Powder-coated
UV-resistant pure polyester - Colour
- RAL 7035
- Supply includes
- Condenser with hydrophobic RiNano coating
Integral electric condensate evaporation
Fully wired ready for connection (plug-in terminal strip)
Mounting frame for universal attachment to outdoor enclosures for external, partial internal and full internal mounting.
Assembly parts - Options
- For remote monitoring and networking of cooling units and chillers in the Blue e+ generation, please use the IoT interface (Model No. 3124.300). Increase machine availability and process reliability with remote monitoring of device data, statuses and system messages.
- Total cooling output to DIN EN 14511
- Cooling output L35 L35/50 Hz: 5 kW
Cooling output L35 L35/60 Hz: 5 kW
Cooling output L35 L50/50 Hz: 3.62 kW
Cooling output L35 L50/60 Hz: 3.62 kW - Rated operating voltage
- 380 V - 480 V, 3~, 50 Hz/60 Hz
- Note
- By downloading the software, a contract is concluded between the contractual partner and Rittal for the free use of the software in accordance with these licence conditions.
- Note on Model No.
- Tolerance: 380 V -10% (342 V) and 480 V +5% (509 V)
- Rated power input
- 2,2 kW
- Power consumption Pel
- Power consumption L35 L35/50 Hz: 2.42 kW
Power consumption L35 L35/60 Hz: 2.42 kW
Power consumption L35 L50/50 Hz: 2.42 kW
Power consumption L35 L50/60 Hz: 2.42 kW - Temperature control
- e+ controller (factory setting +35 °C)
- Dimensions
- Width: 465 mm
Height: 1,640 mm
Depth: 360 mm - Enclosure dimensions including sealing frame and designer cover
- Width: 517 mm
Height: 1,692 mm
Depth: 360 mm - Installation type
- Universal installation (external mounting, partial internal mounting, full internal mounting)
- IP protection category to IEC 60 529
- with mounting frame: internal circuit IP56
- without mounting frame: internal circuit IP 54
- Protection category NEMA
- with mounting frame: UL Type 12/3R/4
- without mounting frame: UL Type 12/3R
- Air throughput (unimpeded air flow)
- External circuit: 2,300 m³/h
Internal circuit: 2,300 m³/h - Refrigerant/cooling medium
- Refrigerant: R134a
Quantity: 1.75 kg
Global Warming Potential (GWP): 1,430
CO₂ equivalent (CO₂e): 2.5 t - Energy efficiency ratio (EER) 50/60 Hz L35 L35
- Refrigeration factor L35 L35 (EER) 50 Hz: 2.07
Refrigeration factor L35 L35 (EER) 60 Hz: 2.07 - To fit
- Enclosure type: Toptec
Width: ≥ 800 mm
Height: ≥ 1,800 mm - To fit Model No.
- 9888.560
- Setting range
- 20 °C...50 °C
- Operating temperature range
- -30 °C...60 °C
- Operating temperature range of refrigerant circuit (active)
- 3 °C...60 °C
- Heat pipe operating temperature range
- -30 °C...45 °C
- Storage temperature range
- -40 °C...70 °C
- Permissible operating pressure (p. max.)
- 2.4
- Noise level
- 71 dB(A)
- Packs of
- 1 pc(s).
- Weight/pack
- 72,8 kg
- Customs tariff number
- 84158200
- EAN
- 4028177964495
- ETIM 8
- EC000855
- ETIM 7.0
- EC000855
- ECLASS 8.0
- 27180704
- Product description
- SK Cooling unit Blue e+, wall-mounted, Outdoor, 5.0 kW, 380-480 V, 3~, 50-60 Hz, aluminium, WHD: 465 x 1640 x 360 mm
- Документация
- Instructions – R-513A
- Instructions – R134a
- Информационни листовки
- Safety data sheet refrigerant – R-513A
- Safety data sheet refrigerant – R134a
Wall-mounted cooling unit Blue e+ Outdoor
Energy-efficient wall-mounted cooling units Blue e+ Outdoor in the
output classes 1500 W to 5000 W.
They offer optimum protection for demanding environments thanks to the
high protection class of IP 56 / UL Type 12/3R/4 and the temperature
range of -30°C to 60°C.
The cooling unit can be mounted in three mounting types (internal
mounting, partial mounting and external mounting), for example on TopTe
project solutions.
Cooling output L35 L35 50/60 Hz: 5,0 / 5,0 kW
Cooling outputL35 L50 50/60 Hz: 3,62 / 3,62 kW
Power consumption L35 L35 50/60 Hz: 2,42 / 2,42 kW
Power consumption L35 L50 50/60 Hz: 2,42 / 2,42 kW
Rated power input: 2,2 kW
Rated operating voltage: 380-480 V, 3~, 50/60 Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions [WxHxD]: 517x1692x360 mm incl. sealing frame and designer
cover
Dimensions [WxHxD]: 465x1640x360 mm
To fit: enclosure type Toptec (Width: = 800 mm, Height: = 1800 mm)
Material: Aluminium AIMg3
Surface finish: Powder-coated, UV-resistant pure polyester
Installation type: Universal installation (internal, partial internal
and external)
Colour: RAL 7035
Energy efficiency ratio (EER) 50/60 Hz: 2,07 / 2,07
Refrigerant / Quantity:R134a / 1,75 kg
Operating temperature range: -30 °C to 60 °C
Setting range: 20 °C to 50 °C
Storage temperature range: -40 °C to 70 °C
IP protection category to IEC 60 529: with sealing frame (Internal
circuit IP 56); without sealing frame (Internal circuit IP 54)
Protection category NEMA: with sealing frame (UL Type 12/3R/4); without
sealing frame (UL Type 12/3R)
Weight: 72,8 kg
Energy-efficient wall-mounted cooling units Blue e+ Outdoor in the
output classes 1500 W to 5000 W.
They offer optimum protection for demanding environments thanks to the
high protection class of IP 56 / UL Type 12/3R/4 and the temperature
range of -30°C to 60°C.
The cooling unit can be mounted in three mounting types (internal
mounting, partial mounting and external mounting), for example on TopTe
project solutions.
Cooling output L35 L35 50/60 Hz: 5,0 / 5,0 kW
Cooling outputL35 L50 50/60 Hz: 3,62 / 3,62 kW
Power consumption L35 L35 50/60 Hz: 2,42 / 2,42 kW
Power consumption L35 L50 50/60 Hz: 2,42 / 2,42 kW
Rated power input: 2,2 kW
Rated operating voltage: 380-480 V, 3~, 50/60 Hz
Temperature control: e+ controller (factory setting +35 °C)
Dimensions [WxHxD]: 517x1692x360 mm incl. sealing frame and designer
cover
Dimensions [WxHxD]: 465x1640x360 mm
To fit: enclosure type Toptec (Width: = 800 mm, Height: = 1800 mm)
Material: Aluminium AIMg3
Surface finish: Powder-coated, UV-resistant pure polyester
Installation type: Universal installation (internal, partial internal
and external)
Colour: RAL 7035
Energy efficiency ratio (EER) 50/60 Hz: 2,07 / 2,07
Refrigerant / Quantity:R134a / 1,75 kg
Operating temperature range: -30 °C to 60 °C
Setting range: 20 °C to 50 °C
Storage temperature range: -40 °C to 70 °C
IP protection category to IEC 60 529: with sealing frame (Internal
circuit IP 56); without sealing frame (Internal circuit IP 54)
Protection category NEMA: with sealing frame (UL Type 12/3R/4); without
sealing frame (UL Type 12/3R)
Weight: 72,8 kg