- Член №.:
- RX 9362421
- Benefits
- Cover: can be locked and prepared for a lead seal 
- Voltage test through separate opening 
- Snap-on mounting up to 250 A and simple adjustment to busbar thickness 5/10 mm 
- Tool-free changeover of the cable outlet 
- Park position for simpler maintenance work 
- All variants also available with electronic fuse monitoring 
- Material
- Polyamide (PA 6)
 Fire protection corresponding to UL 94
 Contact tracks: Electrolytic copper, silver-plated
- Colour
- RAL 9005
 RAL 35745
- For bar systems with centre-to-centre spacing
- 60 mm 
- Cable outlet
- Bottom 
- Type of electrical connection
- Box terminal 
- Rated insulation voltage
- 1 000 V 
- Rated operating current max.
- 125 A 
- Rated operating voltage
- 690 V AC 
- For NH size
- 000 
- Test specification
- IEC/DIN EN 60 947-3 
- DIN EN 60 269-2 (fuse inserts) 
- Dimensions
- Width: 53 mm
 Height: 212 mm
 Depth: 103 mm
- Operating temperature range
- -5 °C...35 °C 
- Storage temperature range
- -25 °C...70 °C 
- To fit busbars
- 15 x 5/10 mm 
- 20 x 5/10 mm 
- 30 x 5/10 mm 
- To fit busbar system
- RiLineX 
- RiLine60 
- Number of poles
- 3-pole 
- Utilisation category
- AC-23B (400 V/100 A) 
- AC-22B (500 V/100 A) 
- null 
- DC-22B (250 V/100 A) 
- Contamination level
- 3 
- IP protection category to IEC 60 529
- IP 2XB 
- Fire load
- 10,84 MJ/m² 
- Connection of round conductors, fine wire without wire end ferrule
- 1.5 ‐ 16 mm² 
- Connection of round conductors, fine wire with wire end ferrule
- 1.5 ‐ 50 mm² 
- Power dissipation (fix)
- 36 W 
- Power dissipation (max.)
- 9 W 
- Packs of
- 1 pc(s). 
- Net weight
- 0,7 kg
- Gross weight
- 0,722 kg
- Copper weight (kg per piece)
- 0,404 
- Customs tariff number
- 85369095 
- ETIM 9
- EC001040 
- Product description
- 
RiLineX NH fuse-switch disconnector in size 000 for 60 mm busbar systems. The cover can be locked and prepared for a lead seal. It also has visual fuse monitoring. Integrated measuring points on the cover ensure safe voltage testing. NH fuse-switch disconnectors have a park position to make maintenance easier. Box terminal connection to connect round conductors ranging from min. 1.5 to max. 50 mm². Cable outlet at the bottom.