Coolant Distribution Unit CDU In-Rack

Référence: SK 3343230

Liquid-to-liquid coolant distribution unit for liquid-cooled high-performance servers. The CDU In-Rack separates the building’s water circuit from the refrigerant circuit of the IT equipment. This ensures that the requisite volumetric flow, pressure and quality of the cooling medium in the secondary circuit are maintained at all times.

Référence:
SK 3343230
Modèle
Refroidissement de baie
Matériau
Tôle d'acier laquée
Couleur
RAL 9005
Composition de la livraison
Ready-to-connect CDU In-Rack (4 OU)
Control module (1 OU)
TCS filter 25 µm
Options
Filter size
Écran
Puissance frigorifique totale
150 kW at 6K ATD
200 kW at 8K ATD
( 511.821 BTU/h at 6K ATD
682.428 BTU/h at 8K ATD )
Nominal flow rate, secondary circuit
225 l/min: at 1.5 bar
Number of pumps and Type of pump
3 Variable Speed Drive (VSD) centrifugal pump
Tension nominale
48 V (DC)
Type de raccordement (électrique)
DC busbar
Dimensions
CDU In-Rack: 548 mm x 188,5 mm x 855 mm
Control Modul: 548 mm x 46,8 mm x 853,4 mm
( CDU In-Rack: 21,6 ˝ x 7,42 ˝ x 33,7 ˝
Control Modul: 21,6 ˝ x 1,84 ˝ x 33,6 ˝ )
Poids en fonctionnement
93 kg
( 205 lb. )
Connexion hydraulique
FWS: 1 1/2" sanitary flange with tri-clamp
TCS: 1 1/2" sanitary flange with tri-clamp
Alimentation en eau
Facility Water System (FWS): Rear
Technical Cooling System (TCS): Rear
Plage de température de service du liquide de refroidissement
FWS: 10 °C...50 °C
TCS: 20 °C...55 °C
( FWS: 50 °F...122 °F
TCS: 68 °F...131 °F )
Liquide de refroidissement
FWS: Water
TCS: Water + PG25
Pression de régime tolérée (p max.)
FWS: 10 bar
TCS: 5 bar
( FWS: 145 PSI
TCS: 72,5 PSI )
Filtre du circuit secondaire
25 µm,optional 50 µm
avec aptitude hot swap
Control Module
Capteurs
Redundant cooling
Pump : N+1
Supervision
Monitoring of all system-relevant parameters such as temperature, humidity, pressure, flow rate, filter, leaks, component status
Protocoles
Redfish
Modbus/TCP
HTTP, HTTPS, SSL, SSH, NTP, Telnet, TCP/IP v4, TCP/IP v6, DHCP, DNS, NTP, Syslog, SNMP v1, SNMP v2c, SNMP v3, OPC-UA, FTP/SFTP, SMTP
LDAP
RCCMD
Surveillance de fuites
Oui
Convient au type d'enveloppe
Baie OCP ORV3
Power consumption (max)
3,2 kW
Unité d'emballage
1 p.
Numéro du tarif douanier
84158200
Description produit
CDU In-Rack, 150 kW at 6K ATD, 548x188.5x855 mm (WHD)