Coolant Distribution Unit CDU In-Rack

Articolul nr.: SK 3343230

Liquid-to-liquid coolant distribution unit for liquid-cooled high-performance servers. The CDU In-Rack separates the building’s water circuit from the refrigerant circuit of the IT equipment. This ensures that the requisite volumetric flow, pressure and quality of the cooling medium in the secondary circuit are maintained at all times.

Articolul nr.:
SK 3343230
Design
Rack cooling
Material
Sheet steel, spray-finished
Colour
RAL 9005
Supply includes
Ready-to-connect CDU In-Rack (4 OU)
Control module (1 OU)
TCS filter 25 µm
Options
Filter size
Display
Total cooling output
150 kW at 6K ATD
200 kW at 8K ATD
Nominal flow rate, secondary circuit
225 l/min: at 1.5 bar
Number of pumps and Type of pump
3 Variable Speed Drive (VSD) centrifugal pump
Rated operating voltage
48 V (DC)
Type of electrical connection
DC busbar
Dimensions
CDU In-Rack: 548 mm x 188.5 mm x 855 mm
Control Modul: 548 mm x 46.8 mm x 853.4 mm
Operating weight
93 kg
Water connections
FWS: 1 1/2" sanitary flange with tri-clamp
TCS: 1 1/2" sanitary flange with tri-clamp
Water supply
Facility Water System (FWS): Rear
Technical Cooling System (TCS): Rear
Operating temperature range of cooling medium
FWS: 10 °C...50 °C
TCS: 20 °C...55 °C
Cooling medium
FWS: Water
TCS: Water + PG25
Permissible operating pressure (p. max.)
FWS: 10 bar
TCS: 5 bar
Filter secondary circuit
25 µm,optional 50 µm
hot swap compatible
Control Module
Sensors
Redundant cooling
Pump : N+1
Monitoring
Monitoring of all system-relevant parameters such as temperature, humidity, pressure, flow rate, filter, leaks, component status
Protocols
Redfish
Modbus/TCP
HTTP, HTTPS, SSL, SSH, NTP, Telnet, TCP/IP v4, TCP/IP v6, DHCP, DNS, NTP, Syslog, SNMP v1, SNMP v2c, SNMP v3, OPC-UA, FTP/SFTP, SMTP
LDAP
RCCMD
Leak monitoring
Da
To fit enclosure type
OCP ORV3 rack
Power consumption (max)
3,2 kW
Packs of
1 pc(s).
Customs tariff number
84158200
Product description
CDU In-Rack, 150 kW at 6K ATD, 548x188.5x855 mm (WHD)