- Numărul articolului:
- RX 9360.525
- Design
- Easy Fix
- Benefits
- Direct mounting of moulded-case circuit-breakers (MCCBs) on the board
- Tool-free changeover of the cable outlet
- Snap-on mounting up to 250 A and simple adjustment to busbar thickness 5/10 mm
- Fast, simple pre-assembly of standard market switch types outside of the enclosure
- High rated voltage 800 V ready
- Material
- Polyamide (PA 6)
Fire protection corresponding to UL 94
- Colour
- RAL 9005
RAL 35745
- Supply includes
- 3 terminal covers
- IP protection category to IEC 60 529
- IP 2XB
- Rated current max.
- 400 A
- Rated current (UL)
- 400 A
- Rated impulse withstand voltage Uimp
- 12 kV
- Rated voltage
- 690 V AC
690 V DC
600 V AC (UL)
- Rated insulation voltage
- 1.000 V
- Rated impulse withstand current
- 80 mA
- Overvoltage category
- 4
- Contamination level
- 3
- Number of poles
- 3-pole
- Cable outlet
- Top/bottom
- Type of electrical connection
- Screw M10
- To fit manufacturer (model)
- ABB (S5 400, S5, T5, XT5, FG400, FG630)
- Chint (NM8N-400, NM8N-630, NXM-400S, NXM-630S, NXMS-400, NXMS-630)
- Eaton (NZM3)
- Fuji Electric (BW400_-3)
- Hager (X630)
- Hyundai Electric (400AF, 400, 630AF)
- LS Electric (400AF, TS400, TS630)
- Mitsubishi (NF400-SW, NF630-SW)
- OEZ (BH630)
- Rockwell (140G-K0F3-D40, 140G-M0F3-D63)
- Schneider (NSX400, NSX630)
- Schrack (MC3)
- Siemens (3VA23, 3VA24)
- Terasaki (S400, E630, S630)
- To fit busbar system
- RiLineX
- RiLine60
- Fundamental frequency
- 50...60 Hz
- Ambient humidity (non-condensing)
- 10...90 %
- To fit busbars
- 15 x 5/10 mm
- 20 x 5/10 mm
- 30 x 5/10 mm
- Operating temperature range
- -25 °C...55 °C
- Storage temperature range
- -25 °C...75 °C
- Dimensions
- Width: 140 mm
Height: 325 mm
- Packs of
- 1 pc(s).
- Net weight
- 4 kg
- Gross weight
- 4,298 kg
- Copper weight (kg per piece)
- 1,652
- Customs tariff number
- 85369095
- EAN
- 4028177997127
- ETIM 9
- EC001531
- Product description
-
RX CB component adaptor 400 A, 3-pole, design: Easy Fix, W: 140 mm