Air/Water Heat Exchangers Wall-mounted HD

Article number: SK 3214.700

Air/water heat exchanger for production areas in the food and beverage industry where hygiene is important – the perfect addition to the Rittal Hygienic Design range. The easy-to-clean design reduces the risk of contamination and ensures food safety.

Quantity PU *

* Packaging unit = 1 pc.

Description
Air/water heat exchanger for production areas in the food sector with high hygienic requirements – the ideal supplement to the Rittal Hygienic Design Program. Its easy-clean design reduces the risk of contamination and guarantees food safety.
Benefits
Easy-clean and hygiene-compliant design
A roof slope of 30° prevents objects from being placed on them and allows liquid to run off quickly.
An all-round external, replaceable silicone seal prevents the build-up of dirt between the enclosure and the air/water heat exchanger.
Material
Housing: Stainless steel 1.4301 (AISI 304)
Surface finish
Housing: Brushed, grain 400, peak-to-valley height < 0.8 µm
Protection category IP to IEC 60 529
IP 56/59
Protection category NEMA
NEMA 4X
Supply includes
Wired ready for connection
Drilling template
Sealing and assembly components
Note
In order to achieve protection category IP 66/69 as per IEC 60 529, the ingress of leakage air through the condensation drain openings must be completely prevented.
Total cooling output
L 35 W 10 at 200 l/h: 0.6 kW ( 2,047BTU )
L 35 W 10 at 400 l/h: 0.65 kW ( 2,217BTU )
Air throughput (unimpeded air flow)
Internal circuit at 50 Hz: 280 m³/h ( 164.8cfm )
Internal circuit at 60 Hz: 310 m³/h ( 182.5cfm )
Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Dimensions
Width: 220 mm ( 8.7" )
Height: 526 mm ( 21" )
Depth: 100 mm ( 3.9" )
Temperature control
Thermostat-controlled solenoid valve
Temperature range
Operation (environment): +1 °C...+70 °C
Setting range: +20 °C...+60 °C
Water inlet: +1 °C...+30 °C
Duty cycle
100 %
Rated power Pel
At 50 Hz: 33 W
At 60 Hz: 34 W
Rated current max.
At 50 Hz: 0.16 A
At 60 Hz: 0.14 A
Miniature circuit-breaker/fuse
2 A
Permissible operating pressure (p. max.)
1 bar - 10 bar
Temperature monitoring
Internal thermostat, with change-over contact, switching load 16 A, setting range +20 °C ... +60 °C (factory setting +35 °C)
Water connections
G ⅜" external thread
eCl@ss 8.0/8.1
27180712
Packaging unit
1 pc(s)
Weight/packaging unit
6 kg ( 13.2lb. )
EAN
4028177806399
Customs tariff number
84158300
ETIM 7.0
EC002515
ETIM 6.0
EC002515
eCl@ss 8.0/8.1
27180712
eCl@ss 6.0/6.1
27180712
Product description
SK Air/water heat exchanger, wall-mounted, HD, 0.65 kW, 230 V, 1~, 50/60 Hz, Thermostat-controlled magnetic valve, WHD: 220 x 526 x 100 mm
Approvals
Approval overview
CSA
UL + C-UL - FTTA
UR + C-UR
Certificates
DGUV
EAC
Declarations
Declaration of conformity