Compact cooling for Micro Data Center

Article number: SK 3126.230

Compact cooling unit suitable for use in rooms with climate control in the building or sufficient ventilation, as well as low or no noise requirements.

Article number:
SK 3126.230
Product description
For cooling of Micro Data Center Level B and Level E. The Split cooling unit consists of an internal unit (condenser) and an external unit. The internal unit is fastened to the side panel inside the Micro Data Center, the external unit is attached to the service door.
Benefits
Separate, hermetically sealed internal and external circuits
No ingress of dust and flue gas
The internal and external units are connected to one another via coolant lines and control cables and are shielded for fire protection
Air routing in the Micro Data Center is horizontal. Adjusted air baffle plates ensure targeted air routing. By separating the "cold side" from the "hot side", air short-circuits are avoided, and the cooling efficiency is increased
Color
RAL 7035
Supply includes
Internal unit (condenser)
External unit
Coolant lines
Data and supply cables
Rated current max.
At 50 Hz: 3.3 A
At 60 Hz: 3.5 A
Total cooling output to DIN EN 14511
2,070 W/2,300 W
( 7,063 BTU/h/7,848 BTU/h )
Start-up current (max.)
At 50 Hz: 14.2 A
At 60 Hz: 14.7 A
Rated power Pel 50/60 Hz L35 L35
1,275 W/1,615 W
Rated power Pel 50/60 Hz L35 L50
1,525 W/1,920 W
Type of connection (electrical)
Plug-in terminal strip
Duty cycle
100 %
Temperature control
Comfort controller (factory setting +25 °C)
At 60 Hz
3.5 A
Motor circuit-breaker
Yes
Noise pressure level
70 dB(A)
OUT_COL_REFRIGERATION_FACTOR_RANGE_L35_L35_50_60HZ
2
Operating temperature range
20 °C...55 °C
( 68 °F...131 °F )
Permissible operating pressure (p. max.)
28 bar
( 406.1 PSI )
Pre-fuse
Miniature circuit-breaker/fuse: 6.3...10 A
Total cooling output to DIN EN 14511
Cooling output L35 L35/50 Hz: 2,500 W
Cooling output L35 L35/60 Hz: 3,090 W
Cooling output L35 L50/50 Hz: 2,070 W
Cooling output L35 L50/60 Hz: 2,300 W
( Cooling output L35 L35/50 Hz: 8,530 BTU/h
Cooling output L35 L35/60 Hz: 10,544 BTU/h
Cooling output L35 L50/50 Hz: 7,063 BTU/h
Cooling output L35 L50/60 Hz: 7,848 BTU/h )
Packaging unit
1 pc(s).
EAN
4028177617742
ECLASS 8.0
27180704
Product description
SK Compact cooling, 8530.36 BTU/h 3~, 400 V, 50 HZ
Documentation
Instructions