- Article number:
- SK 3301.800
- Benefits
- Even air distribution in front of the 482.6 mm (19") level
- Applications
- Cooling of IT equipment in IT enclosures sited as stand-alone units in secondary rooms
- Function principle
- The device supports "front to back" air routing typical of IT applications, and regulates the server inlet temperature to the set value
- The hot waste air from the IT equipment is drawn into the device at the rear of the IT enclosure, cooled, and the cooled air blown back in front of the 482.6 mm (19") level
- Material
- Carbon steel
- Color
- RAL 7035
- Supply includes
- Condenser with hydrophobic RiNano coating
Integral electric condensate evaporation
Wired ready for connection
Drilling template
Air Baffle Plate
Assembly components
- Total cooling output to DIN EN 14511
- Total cooling output L35 L45: 3,200 W( Total cooling output L35 L45: 10,919 BTU/h )
- Air throughput (unimpeded air flow)
- External circuit: 2,000 m³/h
Internal circuit: 1,450 m³/h( External circuit: 1,177.2 cfm
Internal circuit: 853.4 cfm )
- Energy efficiency ratio (EER) 50/60 Hz L35 L35
- Refrigeration factor L35 L35 (EER) 50 Hz: 1.6
- Rated operating voltage
- 230 V, 1~, 50 Hz
- Rated current max.
- At 50 Hz: 10.4 A
- Type of connection (electrical)
- Plug-in terminal strip
- Dimensions
- Width: 597 mm
Height: 417 mm
Depth: 895 mm( Width: 23.5 ˝
Height: 16.4 ˝
Depth: 35.2 ˝ )
- Start-up current (max.)
- At 50 Hz: 36 A
- Duty cycle
- 100 %
- Temperature control
- Control of the server inlet temperature
- Monitoring
- Air intake temperature monitoring
- Permissible operating pressure (p. max.)
- 25 bar( 362.6 PSI )
- Pre-fuse
- Miniature circuit-breaker/fuse: 16 A
- Setting range
- 20 °C...25 °C( 68 °F...77 °F )
- Protection category IP to EN 60 529
- External circuit IP 20
- Internal circuit IP 20
- Refrigerant/cooling medium
- Refrigerant: R134a
Quantity: 1.2 kg
Global Warming Potential (GWP): 1,430( Refrigerant: R134a
Quantity: 2.6 lb. )
- Packaging unit
- 1 pc(s).
- Net weight
- 89 kg
- Gross weight
- 98 kg
- Customs tariff number
- 84158200
- EAN
- 4028177558298
- ETIM 9
- EC000855
- ETIM 8
- EC000855
- ECLASS 8.0
- 27180704
- Product description
-
SK Roof-mounted cooling unit, For cooling IT equipment, Control of the server air infeed temperature, WHD: 597x417x895 mm, 230 V, 1~, 50 Hz