RiLineX connection adapter

Article no.: RX 9360240

RiLineX connection adapter for 60 mm busbar systems. The adapter boasts an impressive compact design. Dismantling requires the use of tools. Conductors may be connected either from above or below. Inserting the connecting conductors couldn't be simpler, thanks to the dividable connection clamp. The adapter may also be used for flat copper bars. Mounted by simply snapping onto the RiLineX board. The adapter is readily installed on RiLine60. It offers high levels of short-circuit protection and easy-to-fit contact hazard protection. The device has a screw fastening for simultaneous contacting of the bar and conductor and for adjusting the busbar thickness (5/10 mm).

Article no.:
RX 9360240
Benefits
Mounting on the busbar system and cable connection with just one screw
Material
Polyamide (PA 6)
Fire behavior corresponding to UL 94
Color
RAL 9005
Rated current (guideline value, IEC)
432 A
Max. rated current of round conductor (IEC)
680 A
Max. rated current of round conductors (UL)
640 A
Max. rated current of laminated copper bar (IEC)
870 A
Max. rated current of laminated copper bar (UL)
840 A
Note
The specified rated current as a guideline value is based on the recommended maximum operating current for single-wire cables with an admissible conductor temperature of 70 °C to IEC 61439-1, Table H.1 when laid horizontally in free air, at an ambient temperature of 55 °C.
The specified max. rated current (IEC) describes the recommended max. operating current of the terminal connection with a temperature rise limit of 70K to IEC 61439-1 (Table 6) for conductors laid in free air with clearance. Please note the maximum admissible insulation temperature.
Electrical UL ratings (SCCR)
27.5 kA - 600 V, RMS, unprotected
100 kA - 600 V, circuit breaker max. 600 A, DIVQ/7
100 kA - 600 V, fuse class L max. 1600 A, JDDZ/7
Cable outlet
Top/bottom
For bar systems with center-to-center spacing
60 mm
Number of poles
3-pole
Suitable for busbar system
RiLineX
RiLine60
Dimensions
Width: 145 mm
Height: 239.4 mm
Depth: 104.6 mm
( Width: 5.71 ˝
Height: 9.43 ˝
Depth: 4.12 ˝ )
Connection of round conductors
95 ‐ 300 mm²
Clamping area for laminated copper bars (W x H)
32 x 20 mm
( 1.26 x 0.79 ˝ )
Suitable for busbars
15 x 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
Rated voltage
1,000 V AC
1,500 V DC
600 V AC (UL)
600 V DC (UL)
Contamination level
3
Standards
IEC/EN 61439-1
UL 508
Rated impulse withstand voltage UImp
12 kV
Rated insulation voltage Ui
1,000 V
Power loss max.
28 W
( 96 BTU/h )
Protection category IP to IEC 60 529
IP 2X
Maximum operating air humidity
90 %
Operating temperature range
-5 °C...55 °C
( 23 °F...131 °F )
Storage temperature range
-25 °C...75 °C
( -13 °F...167 °F )
Ambient humidity (non-condensing)
10...90 %
Fire load
15.903 MJ/m²
Packaging unit
1 pc(s).
Net weight
1.8 kg
Gross weight
1.849 kg
PCF/VE (cradle-to-gate)
10.57
Customs tariff number
85369010
EAN
4028177997219
ETIM 9
EC001531
Product description
RiLineX connection adapter for 60 mm busbar systems. The adapter boasts an impressive compact design. Dismantling requires the use of tools. Conductors may be connected either from above or below. Inserting the connecting conductors couldn't be simpler, thanks to the dividable connection clamp. The adapter may also be used for flat copper bars. Mounted by simply snapping onto the RiLineX board. The adapter is readily installed on RiLine60. It offers high levels of short-circuit protection and easy-to-fit contact hazard protection. The device has a screw fastening for simultaneous contacting of the bar and conductor and for adjusting the busbar thickness (5/10 mm).
Approvals
UL + C-UL (listed)
Declarations
Declaration of conformity
PCF-declaration
Documentation
Instructions
Quick guide
Safety instructions