- Article number:
- SK 3302.300
- Design
- wall-mounted
Horizontal - Product description
- Energy-efficient Blue e wall-mounted cooling units in the output categories 300 W to 4000 W and with integral electrical condensate evaporator (from 1000 W).
- Benefits
- May be linked to the IoT interface via Blue e IoT adaptor for cooling units from 500 W cooling output with e-Comfort controller
- Material
- Sheet steel
- Colour
- RAL 7035
- Supply includes
- Condenser with hydrophobic RiNano coating
Fully wired ready for connection (plug-in terminal strip)
Drilling template
Assembly parts - Total cooling output to DIN EN 14511
- Cooling output L35 L35/50 Hz: 0.3 kW
Cooling output L35 L35/60 Hz: 0.32 kW
Cooling output L35 L50/50 Hz: 0.18 kW
Cooling output L35 L50/60 Hz: 0.19 kW - Rated operating voltage
- 230 V, 1~, 50 Hz/60 Hz
- Rated current max.
- At 50 Hz: 1.6 A
At 60 Hz: 1.7 A - Start-up current max.
- At 50 Hz: 4.3 A
At 60 Hz: 5.3 A - Air throughput (unimpeded air flow)
- External circuit: 310 m³/h
Internal circuit: 310 m³/h - Energy efficiency ratio (EER) 50/60 Hz L35 L35
- Refrigeration factor L35 L35 (EER) 50 Hz: 1
Refrigeration factor L35 L35 (EER) 60 Hz: 1 - Design
- wall-mounted
- Special design
- Horizontal
- Dimensions
- Width: 525 mm
Height: 340 mm
Depth: 153 mm - Protection category to IEC 60 529
- External circuit IP 34
- Internal circuit IP 54
- Protection category NEMA
- UL Type 12
- Refrigerant/cooling medium
- Refrigerant: R134a
Quantity: 0.1 kg
Global Warming Potential (GWP): 1,430
CO₂ equivalent (CO₂e): 0.14 t - Temperature control
- Basic controller (factory setting +35 °C)
- Operating temperature range
- 10 °C...55 °C
- Storage temperature range
- -40 °C...70 °C
- Setting range
- 30 °C...55 °C
- Power consumption Pel
- Power consumption L35 L35/50 Hz: 0.3 kW
Power consumption L35 L35/60 Hz: 0.32 kW
Power consumption L35 L50/50 Hz: 0.34 kW
Power consumption L35 L50/60 Hz: 0.36 kW - Permissible operating pressure (p. max.)
- 25 bar
- Pre-fuse
- Miniature circuit-breaker/fuse: 10 A
- Packs of
- 1 pc(s).
- Weight/pack
- 13 kg
- Customs tariff number
- 84158200
- EAN
- 4028177429796
- ETIM 8
- EC000855
- ETIM 7.0
- EC000855
- ECLASS 8.0
- 27180704
- Product description
- SK cooling unit TopTherm, wall-mounted, horizontal format, 0.36 kW, 230 V, 1~, 50/60 Hz, Sheet steel, WHD: 525 x 340 x 153 mm
Compact wall-mounted cooling units in horizontal format.
Total cooling output L35 L35 50/60 Hz: 0,30 / 0,32 kW
Total cooling output L35 L50 50/60 Hz: 0,18 / 0,19 kW
Power consumption: L35 L35 50/60 Hz: 0,30 / 0,32 kW
Power consumption: L35 L50 50/60 Hz: 0,34 / 0,36 kW
Rated current: 50/60 Hz: 1,6 A / 1,7 A
Rated operating voltage: 230 V, 1~, 50/60 Hz
Temperature control: Basic controller (factory setting +35 °C)
Dimensions [WxHxD]: 525x340x153 mm
Material: Sheet steel
Colour: RAL 7035
Refrigeration factor (EER) 50/60 Hz: 1,00 / 1,00
Refrigerant / Quantity: R134a / 100 g
Operation range: 10 °C to 55 °C
Setting range: 30 °C to 55 °C
Protection category IP to IEC 60 529: Internal circuit IP 54, External
circuit IP 34
Weight: 13 kg
Total cooling output L35 L35 50/60 Hz: 0,30 / 0,32 kW
Total cooling output L35 L50 50/60 Hz: 0,18 / 0,19 kW
Power consumption: L35 L35 50/60 Hz: 0,30 / 0,32 kW
Power consumption: L35 L50 50/60 Hz: 0,34 / 0,36 kW
Rated current: 50/60 Hz: 1,6 A / 1,7 A
Rated operating voltage: 230 V, 1~, 50/60 Hz
Temperature control: Basic controller (factory setting +35 °C)
Dimensions [WxHxD]: 525x340x153 mm
Material: Sheet steel
Colour: RAL 7035
Refrigeration factor (EER) 50/60 Hz: 1,00 / 1,00
Refrigerant / Quantity: R134a / 100 g
Operation range: 10 °C to 55 °C
Setting range: 30 °C to 55 °C
Protection category IP to IEC 60 529: Internal circuit IP 54, External
circuit IP 34
Weight: 13 kg