Coolant Distribution Unit CDU In-Rack

Št. artikla: SK 3343230

Liquid-to-liquid coolant distribution unit for liquid-cooled high-performance servers. The CDU In-Rack separates the building’s water circuit from the refrigerant circuit of the IT equipment. This ensures that the requisite volumetric flow, pressure and quality of the cooling medium in the secondary circuit are maintained at all times.

Št. artikla:
SK 3343230
Zasnova
Hlajenje ohišja
Material
Jeklena pločevina, lakirano
Barva
RAL 9005
Obseg dobave
Ready-to-connect CDU In-Rack (4 OU)
Control module (1 OU)
TCS filter 25 µm
Možnosti
Filter size
Zaslon
Skupna hladilna moč
150 kW at 6K ATD
200 kW at 8K ATD
Nominal flow rate, secondary circuit
225 l/min: at 1.5 bar
Number of pumps and Type of pump
3 Variable Speed Drive (VSD) centrifugal pump
Nazivna delovna napetost
48 V (DC)
Vrsta električne povezave
DC busbar
Mere
CDU In-Rack: 548 mm x 188,5 mm x 855 mm
Control Modul: 548 mm x 46,8 mm x 853,4 mm
Delovna teža
93 kg
Priključki za vodo
FWS: 1 1/2" sanitary flange with tri-clamp
TCS: 1 1/2" sanitary flange with tri-clamp
Dovod vode
Facility Water System (FWS): Rear
Technical Cooling System (TCS): Rear
Delovno temperaturno območje hladilnega medija
FWS: 10 °C...50 °C
TCS: 20 °C...55 °C
Hladilni medij
FWS: Water
TCS: Water + PG25
Dovoljen delovni tlak (p maks.)
FWS: 10 bar
TCS: 5 bar
Sekundarni tokokrog filtra
25 µm,optional 50 µm
združljiv z zamenjavo med delovanjem
Control Module
Senzorji
Redundant cooling
Pump : N+1
Nadzor
Monitoring of all system-relevant parameters such as temperature, humidity, pressure, flow rate, filter, leaks, component status
Protokoli
Redfish
Modbus/TCP
HTTP, HTTPS, SSL, SSH, NTP, Telnet, TCP/IP v4, TCP/IP v6, DHCP, DNS, NTP, Syslog, SNMP v1, SNMP v2c, SNMP v3, OPC-UA, FTP/SFTP, SMTP
LDAP
RCCMD
Nadzor puščanja
Da
Za tip ohišja
OCP ORV3 rack
Power consumption (max)
3,2 kW
Paketi
1 pc(s).
Carinska tarifna številka
84158200
Opis izdelka
CDU In-Rack, 150 kW at 6K ATD, 548x188.5x855 mm (WHD)