- Št. artikla:
- SK 3343230
- Zasnova
- Hlajenje ohišja
- Material
- Jeklena pločevina, lakirano
- Barva
- RAL 9005
- Obseg dobave
- Ready-to-connect CDU In-Rack (4 OU)
Control module (1 OU)
TCS filter 25 µm - Možnosti
- Filter size
Zaslon - Skupna hladilna moč
- 150 kW at 6K ATD
200 kW at 8K ATD - Nominal flow rate, secondary circuit
- 225 l/min: at 1.5 bar
- Number of pumps and Type of pump
- 3 Variable Speed Drive (VSD) centrifugal pump
- Nazivna delovna napetost
- 48 V (DC)
- Vrsta električne povezave
- DC busbar
- Mere
- CDU In-Rack: 548 mm x 188,5 mm x 855 mm
Control Modul: 548 mm x 46,8 mm x 853,4 mm - Delovna teža
- 93 kg
- Priključki za vodo
- FWS: 1 1/2" sanitary flange with tri-clamp
- TCS: 1 1/2" sanitary flange with tri-clamp
- Dovod vode
- Facility Water System (FWS): Rear
- Technical Cooling System (TCS): Rear
- Delovno temperaturno območje hladilnega medija
- FWS: 10 °C...50 °C
TCS: 20 °C...55 °C - Hladilni medij
- FWS: Water
- TCS: Water + PG25
- Dovoljen delovni tlak (p maks.)
- FWS: 10 bar
TCS: 5 bar - Sekundarni tokokrog filtra
- 25 µm,optional 50 µm
- združljiv z zamenjavo med delovanjem
- Control Module
- Senzorji
- Redundant cooling
- Pump : N+1
- Nadzor
- Monitoring of all system-relevant parameters such as temperature, humidity, pressure, flow rate, filter, leaks, component status
- Protokoli
- Redfish
- Modbus/TCP
- HTTP, HTTPS, SSL, SSH, NTP, Telnet, TCP/IP v4, TCP/IP v6, DHCP, DNS, NTP, Syslog, SNMP v1, SNMP v2c, SNMP v3, OPC-UA, FTP/SFTP, SMTP
- LDAP
- RCCMD
- Nadzor puščanja
- Da
- Za tip ohišja
- OCP ORV3 rack
- Power consumption (max)
- 3,2 kW
- Paketi
- 1 pc(s).
- Carinska tarifna številka
- 84158200
- Opis izdelka
- CDU In-Rack, 150 kW at 6K ATD, 548x188.5x855 mm (WHD)
Coolant Distribution Unit CDU In-Rack
Št. artikla: SK 3343230
Liquid-to-liquid coolant distribution unit for liquid-cooled high-performance servers. The CDU In-Rack separates the building’s water circuit from the refrigerant circuit of the IT equipment. This ensures that the requisite volumetric flow, pressure and quality of the cooling medium in the secondary circuit are maintained at all times.