- Št. artikla:
- SK 3343200
- Zasnova
- Hlajenje serije ohišij
- Material
- Jeklena pločevina, lakirano
- Barva
- RAL 9005
- Obseg dobave
- Ready-to-connect CDU In-Row unit
Vent valves
Senzor puščanja - Možnosti
- No. of pump units
Redundant power supply
Connection: Wired
Filter size
Insulated FWS pipework
Emergency off switch - Skupna hladilna moč
- 1.000 kW at 4K ATD
1.500 kW at 6K ATD - Nominal flow rate, secondary circuit
- 1.500 l/min: at 2.0 bar (N+1)
1.875 l/min: at 1.8 bar (N) - Number of pumps and Type of pump
- 15 Variable Speed Drive (VSD) centrifugal pump
- Nazivna delovna napetost
- 200 - 277 V AC, 3~, 50/60 Hz
- 346 - 480 V AC, 50/60 Hz
- 240 - 380 V DC
- Poraba energije (približno)
- 18 kW
- Vrsta električne povezave
- 2 x NEMA L22-30P
- Delovno temperaturno območje
- 5 °C...35 °C
- Stopnja hrupa
- 73,4 dB(A)
- Mere
- null: 600 mm x 2.300 mm x 1.400 mm
- Delovna teža
- 1.250 kg
- Priključki za vodo
- FWS: 4" sanitary flange with tri-clamp
- TCS: 4" sanitary flange with tri-clamp
- Dovod vode
- Facility Water System (FWS): Base or roof
- Technical Cooling System (TCS): Base or roof
- Delovno temperaturno območje hladilnega medija
- FWS: 10 °C...50 °C
TCS: 20 °C...55 °C - Hladilni medij
- FWS: Water
- TCS: Water + PG25
- Dovoljen delovni tlak (p maks.)
- FWS: 10 bar
TCS: 5 bar - Sekundarni tokokrog filtra
- 25 µm,optional 50 µm
- združljiv z zamenjavo med delovanjem
- Pump unit
- Control Module
- Filter
- Senzorji
- Motor of 2-way valve
- Filling pump
- Drain valve
- Redundant cooling
- Pump unit: N+1
- Filter: 2N
- Nadzor
- Monitoring of all system-relevant parameters such as temperature, humidity, pressure, flow rate, filter, leaks, component status
- Protokoli
- Redfish
- Modbus/TCP
- HTTP, HTTPS, SSL, SSH, NTP, Telnet, TCP/IP v4, TCP/IP v6, DHCP, DNS, NTP, Syslog, SNMP v1, SNMP v2c, SNMP v3, OPC-UA, FTP/SFTP, SMTP
- LDAP
- RCCMD
- Nadzor puščanja
- Da
- Paketi
- 1 pc(s).
- Carinska tarifna številka
- 84733080
- Opis izdelka
- CDU In-Row, 1000 kW @ 4K ATD, 600x2300x1400 mm WHD
Coolant Distribution Unit CDU In-Row
Št. artikla: SK 3343200
Liquid-to-liquid coolant distribution unit for cooling liquid-cooled high-performance servers. The CDU In-Row separates the building's water circuit from the refrigerant circuit of the IT equipment. This ensures that the requisite volumetric flow, pressure and quality of the cooling medium in the secondary circuit are maintained at all times.