RiLineX connection adaptor

Št. artikla: RX 9360230

RiLineX connection adaptor for 60 mm busbar systems. The adaptor boasts an impressive compact design and simple conductor connection. Dismantling requires the use of tools. Conductors may be connected either from above or below. The connection clamps support through-wiring. Mounted by simply snapping onto the RiLineX board. The supply leads and adaptors are screw-fastened onto the board together. The connection adaptor features a high current-carrying capacity plus high levels of short-circuit protection and universal contact hazard protection that adapts to the relevant wire gauge. The device has a screw fastening, and is suitable for bar widths of between 5 and 10 mm.

Št. artikla:
RX 9360230
Prednosti
Mounting on the busbar system and cable connection with just one screw
Material
Poliamid (PA 6)
Protipožarna zaščita v skladu z UL 94
Barva
RAL 9005
Nazivni tok (maks.)
375 A
Maks. nazivni tok
630 A
Rated current of round conductor
630 A
Rated current of round conductor (UL)
600 A
Rated current of laminated copper bar
790 A
Rated current of laminated copper bar (UL)
760 A
Električne nazivne vrednosti UL (SCCR)
27,5 kA - 600 V, RMS, unprotected
100 kA - 600 V, circuit breaker max. 400 A, DIVQ/7
100 kA - 600 V, Fuse Class L max. 1200 A, JDDZ/7
Kabelska vtičnica
Top/bottom
Za sisteme palic z razmakom med središči
60 mm
Število polov
3-pole
Za namestitev sistema zbiralnih sponk
RiLineX
RiLine60
Mere
Širina: 126,8 mm
Višina: 239,4 mm
Globina: 104,6 mm
Priklop okroglih vodnikov
95 ‐ 240 mm²
Vpenjalna površina za laminirane bakrene palice (Š x V)
24 x 20 mm
Rated voltage
1.000 V AC
1.500 V DC
600 V AC (UL)
600 V DC (UL)
Kategorija prenapetosti
4
Stopnja kontaminacije
3
Standardi
IEC/EN 61439-1
UL 508
Nazivna impulzna vzdržna napetost Uimp
12 kV
Rated insulation voltage Ui
1.000 V
Izguba toplote maks.
20 W
IP razred zaščite po IEC 60 529
IP 2XB
Maximum operating air humidity
90 %
Delovno temperaturno območje
-5 °C...55 °C
Temperaturno območje shranjevanja
-25 °C...75 °C
Vlažnost okolice (brez kondenzacije)
10...90 %
Paketi
1 pc(s).
Neto teža
1,5 kg
Bruto teža
1,62 kg
PCF na paket (od zibelke do vrat)
8,65
Carinska tarifna številka
85369010
EAN
4028177997233
ETIM 9
EC001531
Opis izdelka
RiLineX connection adaptor for 60 mm busbar systems. The adaptor boasts an impressive compact design and simple conductor connection. Dismantling requires the use of tools. Conductors may be connected either from above or below. The connection clamps support through-wiring. Mounted by simply snapping onto the RiLineX board. The supply leads and adaptors are screw-fastened onto the board together. The connection adaptor features a high current-carrying capacity plus high levels of short-circuit protection and universal contact hazard protection that adapts to the relevant wire gauge. The device has a screw fastening, and is suitable for bar widths of between 5 and 10 mm.
Odobritve
UL + C-UL (listed)
Izjave
Declaration of conformity
PCF-declaration
Dokumentacija
Instructions
Quick guide
Safety instructions