RiLineX connection adaptor

Št. artikla: RX 9360240

RiLineX connection adaptor for 60 mm busbar systems. The adaptor boasts an impressive compact design. Dismantling requires the use of tools. Conductors may be connected either from above or below. Inserting the connecting conductors couldn't be simpler, thanks to the dividable connection clamp. The adaptor may also be used for flat copper bars. Mounted by simply snapping onto the RiLineX board. The adaptor is readily installed on RiLine60. It offers high levels of short-circuit protection and easy-to-fit contact hazard protection. The device has a screw fastening for simultaneous contacting of the bar and conductor and for adjusting the busbar thickness (5/10 mm).

Št. artikla:
RX 9360240
Prednosti
Mounting on the busbar system and cable connection with just one screw
Material
Poliamid (PA 6)
Protipožarna zaščita v skladu z UL 94
Barva
RAL 9005
Nazivni tok (maks.)
432 A
Maks. nazivni tok
680 A
Rated current of round conductor
680 A
Rated current of round conductor (UL)
640 A
Rated current of laminated copper bar
870 A
Rated current of laminated copper bar (UL)
840 A
Električne nazivne vrednosti UL (SCCR)
27,5 kA - 600 V, RMS, unprotected
100 kA - 600 V, circuit breaker max. 600 A, DIVQ/7
100 kA - 600 V, Fuse Class L max. 1600 A, JDDZ/7
Kabelska vtičnica
Top/bottom
Za sisteme palic z razmakom med središči
60 mm
Število polov
3-pole
Za namestitev sistema zbiralnih sponk
RiLineX
RiLine60
Mere
Širina: 145 mm
Višina: 239,4 mm
Globina: 104,6 mm
Priklop okroglih vodnikov
95 ‐ 300 mm²
Vpenjalna površina za laminirane bakrene palice (Š x V)
32 x 20 mm
Za namestitev zbiralnih sponk
15 x 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
Rated voltage
1.000 V AC
1.500 V DC
600 V AC (UL)
600 V DC (UL)
Kategorija prenapetosti
4
Stopnja kontaminacije
3
Standardi
IEC/EN 61439-1
UL 508
Nazivna impulzna vzdržna napetost Uimp
12 kV
Rated insulation voltage Ui
1.000 V
Izguba toplote maks.
28 W
IP razred zaščite po IEC 60 529
IP 2XB
Maximum operating air humidity
90 %
Delovno temperaturno območje
-5 °C...55 °C
Temperaturno območje shranjevanja
-25 °C...75 °C
Vlažnost okolice (brez kondenzacije)
10...90 %
Paketi
1 pc(s).
Neto teža
1,8 kg
Bruto teža
1,849 kg
Carinska tarifna številka
85369010
EAN
4028177997219
ETIM 9
EC001531
Opis izdelka
RiLineX connection adaptor for 60 mm busbar systems. The adaptor boasts an impressive compact design. Dismantling is only possible with the use of tools. Conductors may be connected either from above or below. Inserting the connecting conductors couldn't be simpler, thanks to the dividable connection clamp. The adaptor may also be used for flat copper bars. Mounted by simply snapping onto the RiLineX board. The adaptor is readily installed on RiLine60. It offers high levels of short-circuit protection and easy-to-fit contact hazard protection. The device has a screw fastening for simultaneous contacting of the bar and conductor and for adjusting the busbar thickness (5/10 mm).
Odobritve
UL + C-UL (listed)
Izjave
Declaration of conformity
PCF-declaration
Dokumentacija
Instructions
Quick guide
Safety instructions