- Št. artikla:
- RX 9361315
- Prednosti
- Mounting on the busbar system and cable connection with just one screw
- Material
- Poliamid (PA 6)
Protipožarna zaščita v skladu z UL 94
- Barva
- RAL 9005
- Rated current (guideline value, IEC)
- 864 A
- Max. rated current of round conductor (IEC)
- 1.060 A
- Max. rated current of round conductors (UL)
- 980 A
- Opomba
- The specified rated current as a guideline value is based on the recommended maximum operating current for single-wire cables with an admissible conductor temperature of 70 °C to IEC 61439-1, Table H.1 when laid horizontally in free air, at an ambient temperature of 55 °C.
- The specified max. rated current (IEC) describes the recommended max. operating current of the terminal connection with a temperature rise limit of 70K to IEC 61439-1 (Table 6) for conductors laid in free air with clearance. Please note the maximum admissible insulation temperature.
- Električne nazivne vrednosti UL (SCCR)
- 27,5 kA - 600 V, RMS, unprotected
- 100 kA - 600 V, circuit breaker max. 600 A, DIVQ/7
- 100 kA - 600 V, Fuse Class L max. 2000 A, JDDZ/7
- Kabelska vtičnica
- Top/bottom
- Za sisteme palic z razmakom med središči
- 60 mm
- Število polov
- Single-pole
- Za namestitev sistema zbiralnih sponk
- RiLineX
- RiLine60
- Mere
- Širina: 54,1 mm
Višina: 119,4 mm
Globina: 163,4 mm
- Priklop okroglih vodnikov
- 95 ‐ 300 mm²
- Za namestitev zbiralnih sponk
- 15 x 10 mm
- 20 x 10 mm
- 30 x 10 mm
- Rated voltage
- 1.000 V AC
1.500 V DC
600 V AC (UL)
600 V DC (UL)
- Stopnja kontaminacije
- 3
- Standardi
- IEC/EN 61439-1
- UL 508
- Nazivna impulzna vzdržna napetost Uimp
- 12 kV
- Rated insulation voltage Ui
- 1.000 V
- Izguba toplote maks.
- 105 W
- IP razred zaščite po IEC 60 529
- IP 2X
- Maximum operating air humidity
- 90 %
- Delovno temperaturno območje
- -5 °C...55 °C
- Temperaturno območje shranjevanja
- -25 °C...75 °C
- Vlažnost okolice (brez kondenzacije)
- 10...90 %
- Število povezav
- 2
- Fire load
- 5,947 MJ/m²
- Paketi
- 1 pc(s).
- Neto teža
- 0,8 kg
- Bruto teža
- 0,892 kg
- PCF na paket (od zibelke do vrat)
- 4,47
- Carinska tarifna številka
- 85369010
- ETIM 9
- EC001531
- Opis izdelka
-
RiLineX connection adaptor for 60 mm busbar systems. The connection adaptor is single-pole and fits a double connection (round/sector-shaped conductor). The phase spacing is freely selectable. The unit is suitable for use with L1/L2/L3/N. The adaptor boasts an impressive compact design. Dismantling requires the use of tools. Conductors may be connected either from above or below. The connection clamps support full through-wiring. Mounted by simply snapping onto the RiLineX board. The adaptor is readily installed on RiLine60. It offers high levels of short-circuit protection and easy-to-fit contact hazard protection.