RiLineX NH fuse-switch disconnector

Št. artikla: RX 9362110

RiLineX NH fuse-switch disconnector in size 1 for 60 mm busbar systems. The cover can be locked and prepared for a lead seal. It also has visual fuse monitoring. Integrated measuring points on the cover ensure safe voltage testing. NH fuse-switch disconnectors have a park position to make maintenance easier. Size M10 screw terminal connection. Cable outlet can be at the top or bottom, as required.

Št. artikla:
RX 9362110
Zasnova
For 60 mm busbar systems
Prednosti
Cover: can be locked and prepared for a lead seal
Voltage test through separate opening
Snap-on mounting up to 250 A and simple adjustment to busbar thickness 5/10 mm
Tool-free changeover of the cable outlet
Park position for simpler maintenance work
All variants also available with electronic fuse monitoring
Material
Poliamid (PA 6)
Protipožarna zaščita v skladu z UL 94
Kontakti: elektrolitski baker s srebrno prevleko
Barva
RAL 9005
RAL 35745
Za sisteme palic z razmakom med središči
60 mm
Kabelska vtičnica
Top/bottom
Vrsta električne povezave
Screw M10
Vložki varovalk
NH 1
Nazivna delovna napetost
690 V AC
Za velikost NH
1
Test specification
IEC/DIN EN 60 947-3
DIN EN 60 269-2 (talilne varovalke)
Mere
Širina: 181,5 mm
Višina: 298 mm
Globina: 116,7 mm
Delovno temperaturno območje
-5 °C...35 °C
Temperaturno območje shranjevanja
-25 °C...70 °C
Za namestitev zbiralnih sponk
15 x 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
Za namestitev sistema zbiralnih sponk
RiLineX
RiLine60
Število polov
3-pole
Utilisation category
AC-23B (400 V/100 A)
AC-22B (500 V/100 A)
AC-21B (690 V/100 A)
DC-22B (250 V/100 A)
DC-21B (440 V/100 A)
Stopnja kontaminacije
3
IP razred zaščite po IEC 60 529
IP 2XB
Fire load
36,19 MJ/m²
Izguba toplote maks.
51 W
Heat loss per fuse insert (max.)
23 W
Paketi
1 pc(s).
Neto teža
2,273 kg
Bruto teža
2,448 kg
Teža bakra (kg na kos)
0,8
Carinska tarifna številka
85369095
ETIM 9
EC001040
Opis izdelka
RiLineX NH fuse-switch disconnector in size 1 for 60 mm busbar systems. The cover can be locked and prepared for a lead seal. It also has visual fuse monitoring. Integrated measuring points on the cover ensure safe voltage testing. NH fuse-switch disconnectors have a park position to make maintenance easier. Size M10 screw terminal connection. Cable outlet can be at the top or bottom, as required.
Odobritve
CQC-CCC
Izjave
Declaration of conformity
PCF-declaration
Dokumentacija
Instructions
Quick guide
Safety instructions