RiLineX fuse-switch disconnector D-Switch

Št. artikla: RX 9360824

RiLineX fuse-switch disconnector for 60 mm busbar systems. For use with D 01 (via gauge ring) and D 02 slow fuses (max. 63 A). Also for use with 10 x 38 mm cylindrical fuses via the supplied retaining springs. Integral optical LED fuse monitoring plus electronic fuse monitoring with alarm contacts The switch is lockable in the on and off positions. Spring terminal blocks up to 16 mm² at an angle of 45° enable easier conductor connection. The device is suitable for tool-free snap-on mounting with semi-automatic busbar adjustment for 5 and 10 mm.

Št. artikla:
RX 9360824
Prednosti
Reliable contacting of fuse inserts (without screw caps)
Snap-on mounting and simple adjustment for busbar thickness (5/10 mm)
Optical LED fuse monitoring
Voltage test through separate opening
Maintenance-free tension spring connection up to 16 mm²
Complete contact hazard protection without any additional accessories (such as screw caps)
Material
Poliamid (PA 6)
Protipožarna zaščita v skladu z UL 94
General colour
RAL 35745
RAL 9005
Obseg dobave
4 fuse-switch disconnectors
12 reducers for D 01 fuses
Vrsta električne povezave
Spring terminal
Maks. nazivni tok
63 A
Nazivna delovna napetost
400 V AC
Kabelska vtičnica
Bottom
Število polov
3-pole
Za namestitev sistema zbiralnih sponk
RiLineX
RiLine60
Mere
Širina: 35,8 mm
Višina: 263 mm
Globina: 104,2 mm
Za namestitev zbiralnih sponk
15 x 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
Kategorija prenapetosti
4
Stopnja kontaminacije
3
Standardi
IEC/DIN EN 60 947-3
Rated insulation voltage Ui
800 V
Izguba toplote maks.
5,5 W
IP razred zaščite po IEC 60 529
IP 2XB
Maximum operating air humidity
90 %
Delovno temperaturno območje
-5 °C...55 °C
Temperaturno območje shranjevanja
-25 °C...75 °C
Vlažnost okolice (brez kondenzacije)
10...90 %
Utilisation category
AC-22B (400 V/100 A)
Vložki varovalk
D 02-E 18
Paketi
4 pc(s).
Neto teža
2,232 kg
Bruto teža
2,236 kg
Teža bakra (kg na kos)
0,105
Carinska tarifna številka
85365080
ETIM 9
EC001040
Opis izdelka
RiLineX fuse-switch disconnector for 60 mm busbar systems. For use with D 01 (via gauge ring) and D 02 slow fuses (max. 63 A). Also for use with 10 x 38 mm cylindrical fuses via the supplied retaining springs. Integral optical LED fuse monitoring plus electronic fuse monitoring with alarm contacts The switch is lockable in the on and off positions. Spring terminal blocks up to 16 mm² at an angle of 45° enable easier conductor connection. The device is suitable for tool-free snap-on mounting with semi-automatic busbar adjustment for 5 and 10 mm.
Izjave
Declaration of conformity
PCF-declaration
Dokumentacija
Instructions
Quick guide
Safety instructions