RiLineX Fuse-switch disconnector

Codice prodotto: RX 9363.210

RiLineX NH fuse-switch disconnector in size 2 for mounting plates. The cover can be locked and prepared for a lead seal. It also has visual fuse monitoring. Integrated measuring points on the cover ensure safe voltage testing. NH fuse-switch disconnectors have a park position to make maintenance easier. Size M10 screw terminal connection.

Codice prodotto:
RX 9363.210
Esecuzione
Per installazioni su piastre di montaggio
Vantaggi
Cover: can be locked and prepared for a lead seal
Voltage test through separate opening
Tool-free changeover of the cable outlet
Park position for simpler maintenance work
High rated voltage 800 V ready
All variants also available with electronic fuse monitoring
Materiale
Poliammide (PA 6)
Resistenza al fuoco secondo UL 94
Piste di contatto: rame elettrolitico, argentato
Colore
RAL 9005
RAL 35745
for mounting plate assembly
Connessione cavi
sup/inf
Connessione elettrica
Vite M10
Rated insulation voltage
1.000 kV
Corrente nominale di esercizio max.
400 A
Tensione nominale di esercizio
690 V AC
Per grandezza fusibili NH
2
Test specification
IEC/DIN EN 60 947-3
DIN EN 60 269-2 (fusibili)
Dimensioni
Larghezza: 209 mm
Altezza: 299 mm
Profondità: 129 mm
Range temperatura di esercizio
-5 °C...35 °C
Range di temperatura stoccaggio
-25 °C...70 °C
Numero dei poli
3 poli
Grado di inquinamento
3
Grado di protezione IP secondo IEC 60 529
IP 2XB
Power dissipation (max.)
71 W
Confezione
1 pz.
Peso netto
3,25 kg
Peso lordo
3,452 kg
Quota di rame (kg / pezzo)
1,32
Codice tariffa doganale
85369095
ETIM 9
EC001040
Descrizione prodotto
RX Sezionatori sottocarico per fusibili NH gr. 2, 400 A, tripolari, con vite M10, montaggio su piastra
Descrizioni
Dichiarazione di conformità
Documentazione
Istruzioni
Quick guide
Safety instructions
Fogli di dati
General technical information