RiLineX connection adaptor

Št. artikla: RX 9360241

RiLineX connection adaptor for side infeed from the left or right. For use with vertical mounting of the board or as a corner connector using laminated connection straps. It is also ideal as a T-connection between horizontal and vertical systems. It must not be used with other busbar systems such as RiLine60.

Št. artikla:
RX 9360241
Prednosti
Mounting on the busbar system and cable connection with just one screw
Vertical variant for side infeed to the board
Material
Poliamid (PA 6)
Protipožarna zaščita v skladu z UL 94
Barva
RAL 35745
Rated current (guideline value, IEC)
432 A
Max. rated current of round conductor (IEC)
710 A
Max. rated current of round conductors (UL)
630 A
Max. rated current of laminated copper bar (IEC)
950 A
Max. rated current of laminated copper bar (UL)
910 A
Opomba
The specified rated current as a guideline value is based on the recommended maximum operating current for single-wire cables with an admissible conductor temperature of 70 °C to IEC 61439-1, Table H.1 when laid horizontally in free air, at an ambient temperature of 55 °C.
The specified max. rated current (IEC) describes the recommended max. operating current of the terminal connection with a temperature rise limit of 70K to IEC 61439-1 (Table 6) for conductors laid in free air with clearance. Please note the maximum admissible insulation temperature.
Električne nazivne vrednosti UL (SCCR)
27,5 kA - 600 V, RMS, unprotected
100 kA - 480 V, circuit breaker max. 800 A, DIVQ/7
100 kA - 600 V, Fuse Class L max. 1200 A, JDDZ/7
Kabelska vtičnica
In an axial direction to the board
Za sisteme palic z razmakom med središči
60 mm
Število polov
3-pole
Za namestitev sistema zbiralnih sponk
RiLineX
RiLine60
Mere
Širina: 57,8 mm
Višina: 239,4 mm
Globina: 135,6 mm
Priklop okroglih vodnikov
150 ‐ 300 mm²
Vpenjalna površina za laminirane bakrene palice (Š x V)
32 x 20 mm
Za namestitev zbiralnih sponk
15 x 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
Rated voltage
1.000 V AC
1.500 V DC
600 V AC (UL)
600 V DC (UL)
Stopnja kontaminacije
3
Standardi
IEC/EN 61439-1
UL 508
Nazivna impulzna vzdržna napetost Uimp
12 kV
Rated insulation voltage Ui
1.000 V
Izguba toplote maks.
50 W
IP razred zaščite po IEC 60 529
IP 2X
Maximum operating air humidity
90 %
Delovno temperaturno območje
-5 °C...55 °C
Temperaturno območje shranjevanja
-25 °C...75 °C
Vlažnost okolice (brez kondenzacije)
10...90 %
Fire load
10,554 MJ/m²
Paketi
1 pc(s).
Neto teža
1 kg
Bruto teža
1,185 kg
PCF na paket (od zibelke do vrat)
5,51
Carinska tarifna številka
85369010
EAN
4028177997202
ETIM 9
EC001531
Opis izdelka
RiLineX connection adaptor for side infeed from the left or right. For use with vertical mounting of the board or as a corner connector using laminated connection straps. It is also ideal as a T-connection between horizontal and vertical systems. It must not be used with other busbar systems such as RiLine60.
Odobritve
UL + C-UL (listed)
Izjave
Declaration of conformity
PCF-declaration
Dokumentacija
Instructions
Quick guide
Safety instructions