- Št. artikla:
- RX 9360241
- Prednosti
- Mounting on the busbar system and cable connection with just one screw
- Vertical variant for side infeed to the board
- Material
- Poliamid (PA 6)
Protipožarna zaščita v skladu z UL 94
- Barva
- RAL 35745
- Rated current (guideline value, IEC)
- 432 A
- Max. rated current of round conductor (IEC)
- 710 A
- Max. rated current of round conductors (UL)
- 630 A
- Max. rated current of laminated copper bar (IEC)
- 950 A
- Max. rated current of laminated copper bar (UL)
- 910 A
- Opomba
- The specified rated current as a guideline value is based on the recommended maximum operating current for single-wire cables with an admissible conductor temperature of 70 °C to IEC 61439-1, Table H.1 when laid horizontally in free air, at an ambient temperature of 55 °C.
- The specified max. rated current (IEC) describes the recommended max. operating current of the terminal connection with a temperature rise limit of 70K to IEC 61439-1 (Table 6) for conductors laid in free air with clearance. Please note the maximum admissible insulation temperature.
- Električne nazivne vrednosti UL (SCCR)
- 27,5 kA - 600 V, RMS, unprotected
- 100 kA - 480 V, circuit breaker max. 800 A, DIVQ/7
- 100 kA - 600 V, Fuse Class L max. 1200 A, JDDZ/7
- Kabelska vtičnica
- In an axial direction to the board
- Za sisteme palic z razmakom med središči
- 60 mm
- Število polov
- 3-pole
- Za namestitev sistema zbiralnih sponk
- RiLineX
- RiLine60
- Mere
- Širina: 57,8 mm
Višina: 239,4 mm
Globina: 135,6 mm
- Priklop okroglih vodnikov
- 150 ‐ 300 mm²
- Vpenjalna površina za laminirane bakrene palice (Š x V)
- 32 x 20 mm
- Za namestitev zbiralnih sponk
- 15 x 5/10 mm
- 20 x 5/10 mm
- 30 x 5/10 mm
- Rated voltage
- 1.000 V AC
1.500 V DC
600 V AC (UL)
600 V DC (UL)
- Stopnja kontaminacije
- 3
- Standardi
- IEC/EN 61439-1
- UL 508
- Nazivna impulzna vzdržna napetost Uimp
- 12 kV
- Rated insulation voltage Ui
- 1.000 V
- Izguba toplote maks.
- 50 W
- IP razred zaščite po IEC 60 529
- IP 2X
- Maximum operating air humidity
- 90 %
- Delovno temperaturno območje
- -5 °C...55 °C
- Temperaturno območje shranjevanja
- -25 °C...75 °C
- Vlažnost okolice (brez kondenzacije)
- 10...90 %
- Fire load
- 10,554 MJ/m²
- Paketi
- 1 pc(s).
- Neto teža
- 1 kg
- Bruto teža
- 1,185 kg
- PCF na paket (od zibelke do vrat)
- 5,51
- Carinska tarifna številka
- 85369010
- EAN
- 4028177997202
- ETIM 9
- EC001531
- Opis izdelka
-
RiLineX connection adaptor for side infeed from the left or right. For use with vertical mounting of the board or as a corner connector using laminated connection straps. It is also ideal as a T-connection between horizontal and vertical systems. It must not be used with other busbar systems such as RiLine60.