- 型号:
- RX 9362.422
- 您的获益
- Cover: can be locked and prepared for a lead seal
- Voltage test through separate opening
- Snap-on mounting up to 250 A and simple adjustment to busbar thickness 5/10 mm
- Tool-free changeover of the cable outlet
- Park position for simpler maintenance work
- All variants also available with electronic fuse monitoring
- 材料
- 聚酰胺 (PA 6)
防火性能根据 UL 94
触点轨道:镀银电解铜
- 颜色
- RAL 9005
RAL 35745
- 用于母线系统,中心距离为...
- 60 mm
- 导线出线
- 上面
- 接线方式
- 框型接线柱
- Rated insulation voltage
- 1,000 V
- 最大额定工作电流
- 125 A
- 额定工作电压
- 690 V 交流
- 用于 NH 规格
- 000
- Test specification
- IEC/DIN EN 60 947-3
- DIN EN 60 269-2(保险器熔丝)
- 尺寸
- 宽度: 53 mm
高度: 212 mm
深度: 103 mm
- 工作温度范围
- -5 °C...35 °C
- 贮存温度范围
- -25 °C...70 °C
- 适合于母线
- 15 x 5/10 mm
- 20 x 5/10 mm
- 30 x 5/10 mm
- 适合于母线系统
- RiLineX
- RiLine60
- 极数
- 3 极
- Utilisation category
- AC-23B (400 V/100 A)
- AC-22B (500 V/100 A)
- AC-21B (690 V/100 A)
- DC-22B (250 V/100 A)
- 污染等级
- 3
- 防护等级 IP,符合 IEC 60 529 标准
- IP 2XB
- 圆导线连接,细线无电缆芯线套管
- 1.5 ‐ 16 mm²
- 圆导线连接,细线带电缆芯线套管
- 1.5 ‐ 50 mm²
- Power dissipation (max.)
- 36 W
- 包装单元
- 1 件
- 净重
- 0.65 kg
- 毛重
- 0.706 kg
- 铜成分(kg/件)
- 0.475
- 税率号
- 85369095
- ETIM 9
- EC001040
- 产品描述
-
RX 低压高分断熔断器隔离开关,规格 000,125 A,3 极,电缆出口在上方,框架式端子