NH-zekeringlastscheiders

Artikelnummer: RX 9362.215

RiLineX NH fuse-switch disconnector in size 2 for 60 mm busbar systems. The cover can be locked and prepared for a lead seal. It also has visual fuse monitoring. Integrated measuring points on the cover ensure safe voltage testing. NH fuse-switch disconnectors have a park position to make maintenance easier. Size M10 screw terminal connection. Cable outlet can be at the top or bottom, as required. Includes electronic fuse monitoring.

Artikelnummer:
RX 9362.215
Voordelen
Cover: can be locked and prepared for a lead seal
Voltage test through separate opening
Snap-on mounting up to 250 A and simple adjustment to busbar thickness 5/10 mm
Tool-free changeover of the cable outlet
Park position for simpler maintenance work
High rated voltage 800 V ready
All variants also available with electronic fuse monitoring
Materiaal
Polyamide (PA 6)
Vlamdovend volgens UL 94
Contactbanen: koper, verzilverd
Kleur
RAL 9005
RAL 35745
Levering
Connectors for electronic fuse monitoring
Voor railsystemen met hartafstand
60 mm
Afgaande aansluiting
boven/onder
Aansluiting (elektrisch)
schroef M10
Nominale stroom max.
400 A
Nominale spanning
690 V AC
Voor NH-grootte
2
Test specification
IEC/DIN EN 60 947-3
DIN EN 60 269-2 (smeltpatronen)
Afmetingen
Breedte: 209 mm
Hoogte: 349 mm
Diepte: 135 mm
Bedrijfstemperatuurbereik
-5 °C...35 °C
Opslagtemperatuurbereik
-25 °C...70 °C
Geschikt voor railkoper
15 x 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
Geschikt voor railsysteem
RiLineX
RiLine60
Aantal polen
3-polig
Vervuilingsgraad
3
Beschermklasse IP volgens IEC 60 529
IP 2XB
Leveringseenheid
1 st.
Nettogewicht
6 kg
Brutogewicht
6 kg
Koperaandeel (kg / stuk)
1,75
Douanetariefnummer
85369095
ETIM 9
EC001040
Product omschrijving
RX NH-zekeringlastscheider DIN 2, 400 A, 3-polig, schroef M10, met zekeringbewaking 800 V
Documentatie
Handleiding
Safety instructions
Databladen
Algemene technische informatie