More on the product
Create PDF of this page+ Product description
Material: |
Cu lamina High-purity electrolyte copper F20 Insulation: Highly resistant vinyl compound, elongation 370%, temperature: -30 °C...+105 °C, fire protection corresponding to UL-94 V0, dielectric strength: 20 kV/mm |
---|---|
Length: | 2,000 mm |
Rated current for temperature increase 50 K: | 965 A |
Rated current for temperature increase 30 K: | 730 A |
Rated current for temperature increase 70 K: | 1,155 A |
Note: |
Construction = Number of lamina x lamina width x lamina thickness May be cut individually to required length The conductor temperature of the laminated copper bar is derived by adding the ambient temperature and the temperature increase together. Example: 3565.005 carrying 180 A, i.e. the temperature increases by 30 K. At an ambient temperature of 35 °C, this produces a resultant conductor temperature of 35 °C + 30 K = 65 °C. |
Version – laminated flat copper: |
Number of lamina: 10 Membrane width: 32 mm Membrane thickness: 1 mm |
Packs of: | 1 pc(s). |
Weight/pack: | 6.5 kg |
Copper weight (kg per piece): | 5.73 |
Customs tariff number: | 74071000 |
EAN: | 4028177666801 |
ETIM 7.0: | EC001522 |
ECLASS 8.0: | 27370303 |
Product description: | SV Laminated copper bar, WH: 32x10 mm, L: 2000 mm |