RiLineX board

Art. nr.: RX 9360024

RiLineX complete board 550 A including busbars 30x5 mm. Length 1105 mm for 1200 mm wide enclosures. End-to-end contact hazard protection up to IP 2XB, upgradable to IP 3X. Suitable for mounting horizontally, vertically and above head height. For voltages up to 1000 V AC and 1500 V DC. Tested short-circuit resistance up to 65 kA. Supports cable routing in the rear section. IEC and UL approved.

Art. nr.:
RX 9360024
Fördelar
Time savings thanks to fully digital product data
Reduced assembly time thanks to pre-assembled complete board
Suitable for applications up to 1000 V AC and up to 1500 V DC
Tested short-circuit resistance up to 65 kA
Contact hazard protection up to IP 2XB, upgradable to IP 3X
Tested and certified to IEC and UL
Simple extension and baying
Material
Polyamid (PA 6)
Brandklassad enligt UL 94
E-Cu
Färg
RAL 35745
RAL 9005
Leveransens omfattning
Integrerade samlingskenor
Kapslingsklass IP enligt IEC 60 529
IP 2XB
Standarder
IEC 61 439-1/-2
UL 508
Märkström max.
550 A
Märkström (UL)
540 A
Elektriska värden UL(SCCR)
45 kA - 600 V, RMS
100 kA - 600 V, säkring klass L max 1600 A, JDDZ/7
100 kA - 600 V, circuit breaker max. 600 A, DIVQ/7
100 kA - 480 V, circuit breaker max. 800 A, DIVQ/7
65 kA - 600 V, circuit breaker max. 800 A, DIVQ/7
Samlingsskenornas mellanavstånd
60 mm
Märkstötspänning Uimp
12 kV
Rated voltage
1 000 V AC
1 500 V DC
600 V AC (UL)
600 V DC (UL)
Rated insulation voltage
1 000 V AC
1 500 V DC
Rated impulse withstand current
115,5 kA
94,5 kA (UL)
Rated short-term withstand current/t
45 kA/500 ms
Överspänningskategori
4
Nedsmutsningsgrad
3
Busbar dimensions
30 mm x 5 mm
Poltal
3-polig
Frekvens för grundtonssvängning
50...60 Hz
Luftfuktighet (ej kondenserande)
10...90 %
Driftstemperatur
-5 °C...55 °C
Förvaringstemperatur
-25 °C...75 °C
Dimension
Bredd: 1.105 mm
Höjd: 246 mm
Djup: 49 mm
Förpackningsenhet
1 st.
Nettovikt
9,5 kg
Bruttovikt
10,2 kg
Kopparandel (kg/st)
4,419
Tullvarukod
85369010
EAN
4028177997400
ETIM 9
EC001900
Produktbeskrivning
RiLineX complete board 550 A including busbars 30 x 5 mm. Length 1105 mm for 1200 mm wide enclosures. Simple, fast baying of multiple boards using RiLineX baying connectors, without reducing short-circuit protection. Cables (such as control lines) may also be routed in the rear section of the board, for added flexibility with system assembly. Comprehensive digital product data means significant time savings with planning and documentation. The board is IEC 61439 and UL 508-approved and may be mounted horizontally, vertically and overhead. What’s more, the system is easily extendible. It is suitable for AC applications up to 1000 V AC and DC applications up to 1500 V DC, offering a versatile solution for a wide range of application areas. The supply includes a preconfigured board and busbars.
Godkännanden
UL + C-UL (listed)
Förklaringar
Konformitetsförklaring
Dokumentation
Manual
Quick guide
Safety instructions
Datablad
Allmän teknisk information