RiLineX NH fuse-switch disconnector

Art. nr.: RX 9362.215

RiLineX NH fuse-switch disconnector in size 2 for 60 mm busbar systems. The cover can be locked and prepared for a lead seal. It also has visual fuse monitoring. Integrated measuring points on the cover ensure safe voltage testing. NH fuse-switch disconnectors have a park position to make maintenance easier. Size M10 screw terminal connection. Cable outlet can be at the top or bottom, as required. Includes electronic fuse monitoring.

Art. nr.:
RX 9362.215
Fördelar
Cover: can be locked and prepared for a lead seal
Voltage test through separate opening
Snap-on mounting up to 250 A and simple adjustment to busbar thickness 5/10 mm
Tool-free changeover of the cable outlet
Park position for simpler maintenance work
All variants also available with electronic fuse monitoring
Material
Polyamid (PA 6)
Brandklassad enligt UL 94
Kontaktbanor: försilvrad elektrolytkoppar
Färg
RAL 9005
RAL 35745
Leveransens omfattning
Connectors for electronic fuse monitoring
För skensystem med centrumavstånd
60 mm
Kabelutgång
uppe/nedtill
Anslutningstyp (elektrisk)
Skruv M10
Märkström max.
400 A
Märkspänning
690 V AC
För NH-storlek
2
Test specification
IEC/DIN EN 60 947-3
DIN EN 60 269-2 (säkringsinsatser)
Dimension
Bredd: 209 mm
Höjd: 349 mm
Djup: 135 mm
Driftstemperatur
-5 °C...35 °C
Förvaringstemperatur
-25 °C...70 °C
Passar för samlingsskenor
15 × 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
Passar för samlingsskenesystemet
RiLineX
RiLine60
Poltal
3-polig
Nedsmutsningsgrad
3
Kapslingsklass IP enligt IEC 60 529
IP 2XB
Power dissipation (max.)
98 W
Förpackningsenhet
1 st.
Nettovikt
4,2 kg
Bruttovikt
4,268 kg
Kopparandel (kg/st)
1,75
Tullvarukod
85369095
ETIM 9
EC001040
Produktbeskrivning
RiLineX NH fuse-switch disconnector in size 2 for 60 mm busbar systems. The cover can be locked and prepared for a lead seal. It also has visual fuse monitoring. Integrated measuring points on the cover ensure safe voltage testing. NH fuse-switch disconnectors have a park position to make maintenance easier. Size M10 screw terminal connection. Cable outlet can be at the top or bottom, as required. Includes electronic fuse monitoring.